FOR THE DESIGN OF SMOKE VENTILATION SYSTEMS FOR SINGLE STOREY INDUSTRIAL BUILDINGS, INCLUDING THOSE WITH MEZZANINE FLOORS, AND HIGH RACKED STORAGE WAREHOUSES
----------------------- Page 1-----------------------
GUIDANCE FOR THE DESIGN OF
SMOKE VENTILATION SYSTEMS FOR
SINGLE STOREY INDUSTRIAL BUILDINGS,
INCLUDING THOSE WITH MEZZANINE FLOORS,
AND HIGH RACKED STORAGE WAREHOUSES
produced by
SMOKE VENTILATION ASSOCIATION
of HEVAC Manufacturers
Issue 3
Published by the Federation of Environmental Trade Associations
All rights reserved. No part of this publication may be
reproduced, stored in a retrieval system, or transmitted in any
form or by any means, electronic, mechanical, photo-copying,
recording or otherwise, without the prior permission of the
Federation of Environmental Trade Associations, Sterling House,
6 Furlong Road, Bourne End, Bucks, SLS 5DG.
CONTENTS
PAGE
10.03.94
SVAIND3.394
----------------------- Page 2-----------------------
FOREWORD 1
1 SCOPE 1
2 DEFINITIONS 1
3 DESIGN PARAMETERS 3
4 FIRE SIZE 4
4.1 INDUSTRIAIL BUILDINGS -
(EXCLUDING HIGH RACKED STORAGE WAREHOUSES) 4
4.2 HIGH RACKED STORAGE WAREHOUSES 6
5 TOTAL HEAT OUTPUT OF FIRES 6
6 CONVECTIVE HEAT OUTPUT 8
7 CLEAR LAYER 8
7.1 INDUSTRIAL BUILDINGS -
(EXCLUDING HIGH RACKED WAREHOUSES) 8
7.2 HIGH RACKED STORAGE WAREHOUSES 9
8 SMOKE COMPARTMENT 12
8.1 BUILDINGS WITHOUT MEZZANINE FLOORS 12
8.2 BUILDINGS WITH MEZZANINE FLOORS 12
9 SPRINKLERS 13
9.1 INDUSTRIAL BUILDINGS -
(EXCLUDING HIGH RACKED STORAGE WAREHOUSES) 13
9.2 HIGH RACKED STORAGE WAREHOUSES 13
9.2.1 CEILING LEVEL SPRINKLERS 14
9.2.2 ESFR SPRINKLERS 14
9.2.3 IN-RACK SPRINKLERS 15
10.03.94
SVAIND3.394
----------------------- Page 3-----------------------
PAGE
10 DEPTH OF SMOKE LAYER 17
10.1 INDUSTRIAL BUILDINGS -
(EXCLUDING HIGH RACKED STORAGE WAREHOUSES) 17
10.2 HIGH RACKED STORAGE WAREHOUSES 17
11 AMBIENT TEMPERATURE l8
12 AIR INLETS/REPLACEMENT AIR l8
13 WIND EFFECTS l8
14 SPECULATIVE BUILDINGS l8
15 SIZING/SITING OF EQUIPMENT 20
16 CONTROLS 20
17 MEZZANINE FLOORS 21
17.1 CLEAR LAYER 21
17.2 PERMEABLE MEZZANINE FLOORS 22
17.3 SOLID (NON-PERMEABLE) MEZZANINE FLOORS 22
APPENDIX 1 - ASSOCIATED BRITISH STANDARDS 27
APPENDIX 2 - REFERENCES 28
APPENDIX 3 - CLASSIFICATION OF SPRINKLER CATEGORIES
FOR INDUSTRIAL BUILDINGS 30
APPENDIX 4 - RATES OF HEAT RELEASE FOR VARIOUS FUELS 33
10.03.94
SVAIND3.394
----------------------- Page 4-----------------------
- 1 -
FOREWORD
The use of smoke and heat exhaust ventilators has been
widespread and their value in assisting in the evacuation
of people from buildings, reducing fire damage and financial
loss by preventing smoke logging, facilitating fire fighting,
reducing roof temperatures and retarding the lateral spread
of fire is firmly established. Therefore, it is essential
that the purpose of the scheme is identified.
The members of the Smoke Ventilation Association have had
many years of interpreting and applying the various design
principles included in the many publications dealing with
smoke control. Based on this experience, the Guide sets out
their recommendations for design considerations. Actual
methods of calculation are set out in various Fire Research
Station (FRS) papers, which are referred to in the text and
listed in Appendix 2.
No scheme will work satisfactorily unless it is correctly
installed and maintained.
1 SCOPE
This guide covers Single Storev Industrial Buildings such as
Factories and Warehouses, including such buildings which
contain Mezzanine Floors, and High Racked Storage Warehouses.
2 DEFINITIONS (see Appendix 1 Reference 1)
DESIGN FIRE SIZE The base dimensions of the largest fire
with which a smoke ventilation system
should be expected to cope. A Design Fire
is normally taken to be square or
circular.
HEAT OUTPUT The total heat generated by the fire
source, including that which may appear
at any point downstream (see also 2.7).
CLEAR LAYER The vertical distance between floor level
and the bottom of the smoke layer.
SMOKE Region of ceiling or roof void isolated
COMPARTMENT from other areas, by building structures
and/or purpose made screens designed to
to prevent the flow of smoke from the
compartment.
SMOKE LAYER The vertical distance from the "centroid"
DEPTH of the extractor (whether horizontal or
vertical plane) to the bottom of the
smoke layer.
10.03.94
SVAIND3.394
----------------------- Page 5-----------------------
- 2 -
REPLACEMENT AIR Cool, ambient temperature, smoke free air
entering the Smoke Compartment during
course of operation of Smoke Ventilation
System to replace the exhausted hot
smoke.
HEAT FLUX The total heat energy carried by the
gases across a specified boundary. This
flux can be convective, radiative and/or
conductive, or a combination thereof.
There is a further form, often referred
to as a "potential" heat flux. This may
be defined as the flow across a specified
boundary of energy yet to be converted to
heat by the fire process.
HEAT LOSS The total heat transferred away from
a body (including gas) through its
boundaries by convection, radiation
and/or conduction, or a combination
thereof, eg heat loss from a gas layer
can be by radiation, convection and
conduction to its surroundings.
CONVECTIVE HEAT That portion of the total heat output
FLUX retained within the flowing gases
immediately outside the combustion
region. This heat flux is, of course,
subject to consequent heat loss.
SMOKE CURTAINS (See Appendix 1 Reference 2)
/SCREENS These are employed as part of a smoke
control system to create ceiling
reservoirs from which smoke and hot
gases can be extracted.
AERODYNAMIC The "Measured Free Area" of the natural
FREE AREA heat and smoke exhaust ventilator
multiplied by the "Coefficient of
Discharge".
MEASURED FREE The actual measured throat area of the
natural heat and smoke exhaust
ventilator: This is the smallest clear
opening normally between the drainage
channels. No reduction should be made
for controls,1ouvres and/or other
obstructions, providing their obstruction
is allowed for in the coefficient of
discharge.
COEFFICIENT OF The ratio of Actual Flow Rate to
DISCHARGE Theoretical Flow Rate through a natural
heat and smoke exhaust ventilator.
10.03.94
SVAIND3.394
----------------------- Page 6-----------------------
- 3 -
CONVECTIVE HEAT Heat content of smoke, calculated as
OUTPUT convective heat flux for a design fire
minus subsequent heat losses. Normally
considered as the value to be used
fordesign purposes.
MEZZANINE An intermediate floor level between the
ground floor level and the roof space of
a single storey industrial building. this
mezzanine floor level to be open to the
remainder of the building so that smoke
will pass freely from one area to the
other and thereby hamper the safe
evacuation of the occupants of the upper
levels in a fire.
HEIGHT OF The vertical distance from the floor
MEZZANINE to the underside of the lowest solid
mezzanine floor level.
PERMEABLE A mezzanine floor which has at least 25%
MEZZANINE of its total plan area evenly distributed
FLOORS as free area for the passage of smoke.
SOLID MEZZANINE A mezzanine floor which is either solid
FLOOR or does not meet the criteria for an
open mezzanine floor.
FLASHOVER A condition when the temperature of the
gases contained in the smoke layer is
sufficiently high to cause spontaneous
ignition (generally due to downward
radiation of heat) of materials not
directly involved in the fire. This
condition should be avoided for obvious
reasons. It is normally considered to be
when the smoky gas layer temperature is
in the region of 500 - 600 degrees
centigrade.
CEILING JET A horizontally flowing layer of hot gases
driven in part by the kinetic energy of
the initially vertically rising fire
plume. It typically has a depth of
approximately 1/lOth of the building
height flowing radially away from the
plume axis.
10.03.94
SVAIND3.394
----------------------- Page 7-----------------------
- 4 -
3 DESIGN PARAMETERS
Fire Size
Heat Output of Fire (convective) Clear Layer
Smoke Compartments
The Effect of Sprinklers
Depth of Smoke Layer
Ambient Temperature
Air Inlets/Replacement Air Wind Effects
Speculative Buildings Sizing/Siting of Equipment Controls
Mezzanine Floors
4 FIRE SIZE
4.1 Industrial Buildings
(Excluding High Racked Storage Warehouses)
4.1.1 Calculations should be based on a steady state
fire condition.
4.1.2 No scheme should be designed on a fire size of less
than 3m x 3m, unless there is a known or isolated
fire risk whose size is known, ie Quench Tank,
Spray Booth etc.
4.1.3 It is recommended that for sprinklered buildings
one of the following steady state fire sizes in
Table 1 is used.
TABLE 1 - STEADY STATE FIRE SIZES
Hazard Fire Size Perimeter Approx Examples of
Category Area Occupancy
(m²) (see also
Appendix 3)
Group 1 3.0 x 3.0m 12m 9 Breweries
Group 2 4.5 x 4.5m 18m 20 Bakeries
Group 3 6.0 x 6.0m 24m 36 Cotton Mills
Group 4 9.0 x 9.0m 36m 81 Paint Manuf’ring
Group 5/1 3.0 x 3.0m 12m 9 Electrical W’house
Group 5/2 4.5 x 4.5m 18m 20 Pharmaceutical W’hse
Group 5/3 6.0 x 6.0m 24m 36 Paper Storage W’hse
Group 5/4 9.0 x 9.0m 36m 81 Plastic Foam W’house
10.03.94
SVAIND3.394
----------------------- Page 8-----------------------
- 5 -
In unsprinklered premises there is the possibility that, in
the absence of effective suppression (eg. sprinklers), the
fire may grow unchecked and eventually destroy the building.
In this instance the detection of the fire is paramount, and
human detection should not be relied upon. Hence a fire/smoke
detection system is recommended to:
(a) raise the alarm both within the building and with the
fire brigade;
(b) initiate the operation of the venting system
The fire may then develop if unchecked to a size at fire
service intervention which will be dependent upon:
(i) the nature of the goods, ie.
combustibility, burning.rate, radiation
output, etc;
(ii) the disposition of the burning material
with respect to other combustibles;
(iii) the geometry of the building
(eg. ceiling height etc);
(iv) the attendance and deployment time of the
fire service
An assessment of the largest likely fire size that the fire
service will encounter should be based upon the above
variables. In the absence of sufficient information or other
guidance being available (eg. British Standards), it is
suggested that the fire size for an unsprinklered fire be
taken as being twice the area of its sprinklered counterpart,
eg. a fire in a Group 3 hazard should be taken as 70m² area
(8.5m x 8.5m). An upper limit of around l00m² (lOm x lOm) may
be considered as an arbitrary maximum beyond which the venting
system will produce no further tangible benefit, other than to
assist fire-fighting operations.
Fire sizes outside these are not normally considered, and in no
circumstances should the design fire size for an unsprinklered
fire be less than that for a sprinklered fire of the same
hazard rating.
10.03.94
SVAIND3.394
----------------------- Page 9-----------------------
- 6 -
4.2 High Racked Storage Warehouses
4.2.1 The potential for fire growth needs to be fully
considered since it is much greater within racked
goods than with materials stored only at ground
level.
Thus for high racked storage systems that do not
employ in-rack or ESFR sprinkler systems the
assumed minimum fire size should not be less than
3m x 3m, and this minimum size should only be
considered in exceptional circumstances.
4.2.2 The nature of the stored goods is vital in the
consideration of the fire size.
4.2.3 The type of packaging material must be
considered in the assessment of the fire size.
4.2.4 The manner of the storage wil1 affect the
potential fire size. For example, paper rolls
stored upright', ie with the hole in the centre
vertical, will allow the fire to grow much faster
than if the paper is stored horizontally.
4.2.5 The surface area of material which can support
combustion must be considered.
4.2.6 The type of sprinkler system to be installed will
affect the fire size selected. See clause 9.
5 TOTAL HEAT OUTPUT OF FIRES
5.1 Figures for the heat release rate (RHR) of known fuel
combinations were compiled for various storage and
process risks in industrial buildings by the Fire
Research Station (see Appendix 2, Reference 1), but
Were categorised in a way unhelpful to smoke control
designers. These data were later revised to provide the
necessary basis for smoke control design (see Appendix 2,
Reference 2). The National Fire Prevention Association
(NFPA) of America have similarly compiled RHRs for
various fuels following experiments (see Appendix 2,
Reference 3). Further data for specific fuels have also
been compiled by the FRS (see Appendix 2, Reference 4).
Appendix 4, Tables A4.1-A4.3 list the various fuels and
fuel arrays, from both UK and USA references.
5.2 For storage risks there is a wide range of values of RHR
for essentially very similar storage categories, eg.
goods stacked in cardboard cartons.
10.03.94
SVAIND3.394
----------------------- Page 10-----------------------
- 7 -
TO BE EDITED
It is a fundamental principle of smoke ventilation that the RHR
chosen for the design fire will affect the calculated
ventilation area or rate of exhaust. Storage risks may also
vary from the initially chosen fuel, eg. glassware in cardboard
cartons to plastic components in cardboard cartons. The nature
of the occupancy (risk) will not have changed (ie. storage),
but the potential RHR will, perhaps reducing the value of the
smoke control system. This can, to a certain extent, be
alleviated by designing the system to deal with the worst-case
scenario for the risk. Table 2 provides the data in Table A4.1
(storage risks) in terms of upper and lower limits for the
various storage categories. The values provided are RHR per
square metre (plan area) for each metre height of storage.
TABLE 2 RATES OF HEAT RELEASE FOR VARIOUS STORAGE CATEGORIES,
PER METRE HEIGHT OF FUEL
Range of RHR
Storage
(kW/m²/m)
Loose wood & wood products,
Inc. wood cribs & pallets;
Upright wood storage. 1800 - 2900
Stacked wood & wood products,
Inc. furniture; books;
Crated objects. 30 - 720
Cardboard & paper products,
Inc. stacked or loose
cardboard boxes or cartons
which are empty; cardboard
tubes or reels; mailbags, 120 - 240
Any storage in cardboard boxes
or cartons*. 160 - 1200
Loose or stacked plastic
prodcuts, inc. PP & PE films
in rolls; PU & PS Insulation
Boards; PE Trays. 260 - 1280
* NB Excludes the apparently anomalously high values for
PS jars in cartons.
The total heat output is calculated from the product of the
plan area of the fire, its height and the appropriate RHR
values.
10.03.94
SVAIND3.394
----------------------- Page 11-----------------------
- 8 -
5.3 Where information on the exact nature of the fuel
Is unknown, eg. speculative buildings, and the local
regulatory authorities have not recommended the design
fire size and RHR, then a range of RHR of 60-500kW/m²/m
is recommended, with a minimum ·assumed storage height of
2m (see Appendix 2, Reference 5). Further design details
for speculative buildings may be found in Section 14.
5.4 The designer should use both values of RHR from Table 2
for the particular occupancy examined, or as in 5.3 above
for speculative buildings, and calculations performed to
determine all of the necessary design parameters. From
these two sets of results, the worst case parameters
resulting from either value of total heat output should
then be used in the design.
5.5 For specific non-storage occupancy or liquid fuel risks,
then the RHRs in Tables A4.2 and A4.3 should be used to
determine the total heat output.
6 CONVECTIVE HEAT OUTPUT
When heat is given off some of it is lost to the structure
and contents by radiation from the hot gas plume. If the roof
reservoir compartments exceed 2000m² in plan area then
consideration should also be given to the radiative and
conductive losses from the established smoke layer to the
roof structure (see Appendix 2 Reference 6).
The convective heat output of the fire is determined by
applying a correction factor to the total heat output
(see Section 5).
Various technical papers give differing values for the heat
loss correction factor. Further research is desirable but, in
the meantime, a 20 percent loss should be applied. For roof
areas greater than the recommended smoke compartment size,
calculations of the heat lost from the smoke layer should be
provided to support the increase in recommended reservoir
size such as a Newtonian heat transfer coefficient method
(see Appendix 2 Reference 7).
7 CLEAR LAYER
7.1 Industrial Buildings excluding High Racked Warehouses
7.1.1 The minimum clear layer should be 3.0m. This is
to permit the escape of personnel and the entry
of fire fighters. Note, however, that the
maximum clear height which car be physically
achieved is 80-90o of the building's height,
due to the presence of the ceiling jet in the
smoke layer (see Appendix 2 Reference 7).
- 9 -
10.03.94
SVAIND3.394
----------------------- Page 12-----------------------
7.1.2 Where the chances of spontaneous ignition and
flashover present a considered risk, and the
maximum clear height available permits it, the
clear layer should extend at least SOOmm above
the stacked goods.
7.1.3 To avoid disruption of the smoke layer in any
single compartment, the base of the smoke layer
should be at least 1-2m above any door/opening
which might either by design or chance be a
source for replacement air, unless the incoming
air velocity is less than lm/s, in which
instance it should be no less than SOOmm above
the opening.
7.1.4 Where the floor level changes within a
compartment, the height of rise should be
measured from the shallowest end for safety
purposes and the overall height from the
deepest end for the entrainment calculation.
7.1.5 Special considerations are necessary when
designing for-mezzanine floors. Note the
comments contained within the Design Parameters
for Mezzanine Floors.
7.2 High Racked Storage Warehouses
7.2.1 In sprinklered warehouses, the system
objectives must be clearly defined for a design
to be produced. These objectives may be to.
(a) Protect personnel within the building, by
ensuring that their escape routes remain
unaffected by smoke;
(b) Protect stock and materials which may be
combustible or salvageable;
(c) Facilitate fire-fighting operations.
7.2.2 For objective (a) to be achieved the design
approach can be either 7.2.2.1 and 7.2.2.3 or
7.2.2.2 and 7.2.2.3.
7.2.2.1 (1) Ensure that the smoke layer is is
established well above head height
ie >lOm above the floor or highest
exposed walkway (other than those used
for infrequent maintenance purposes).
- 10 -
10.03.94
SVAIND3.394
----------------------- Page 13-----------------------
(ii) Provide no reservoir compartment sub-
divisions but ensure that the additional
heat losses from the smoke layer due to
the extended layer area are accounted
for, using a calculation technique which
takes into account convective and
radiative heat transfer from the layer
to the buildings fabric and atmosphere.
The final smoke layer temperature should
o
not be less than 20 C above the average
roof level ambient temperature.
The relaxation on compartmentation is
based on the assumption that escaping
personnel will be able to travel hrough,
and out of, the building without being
detrimentally affected (psychologically)
by the presence of the smoke layer above
their heads, by virtue of its height
above the floor and the nature of their
escape routine, (ie regimented and
practiced escape drill).
(iii) Ensure that an adequate fail-safe low
level inlet air supply is available at
all times, except where reservoir sub-
division are used for this purpose (see
clause 12). Note. It should be
remembered that low level doors/windows
may be secured and low level inlets may
be partially blocked by stored materials.
7.2.2.2 (i) Where it is desirable for the smoke
layer to descend below lOm above the
floor, then the minimum height of rise
should be 3m, and screen separation of
the roof space into reservoirs not
exceeding 60m in the direction of escape
is required. Note, if the plan area of
the reservoirs is greater than 2000m²,
consideration should be given to the
heat losses sustained by the layer.
(ii) In exceptional circumstances it may be
impractical to install such screens. In
these instances alternative smoke ontrol
solutions may be considered, and etailed
calculations shall be provided in
support of any alternative strategy.
10.03.94
SVAIND3.394
----------------------- Page 14-----------------------
- 11 -
7.2.2.3 All life safety systems should operate on
smoke detection and where possible sprinkler
flow switch.
7.2.3 For objective (b) to be achieved the design
approach can be.
(i) Ensure that the design smoke layer is
established above the salvageable stock
levels (except in the instance where this
will result in a smoke layer depth less
than 1/lOth the building height,
see 7.2.5 below).
(ii) Provide screen separation of the roof
space into reservoirs not exceeding
3000m². Where for practical purposes it
is desirable to exceed this area, the
heat losses from the layer should be
taken into account (see 7.2.2.1 (ii)
above). The final design smoke layer
temperature should not be less than 20C
above the average roof level temperature.
(iii) The inlet air supply may be provided from
adjacent, unused reservoirs, or dedicated
low-level openings.
(iv) The venting system should preferably be
operated by a smoke detection system, but
as a minimum should operate on sprinkler
flow switch for in-rack sprinklers, smoke
detectors for roof mounted sprinklers or
on both.
7.2.4 For objective (c) to be achieved the design
approach can be as per objective (a) (see 7.2.2
above), with the exception that smoke reservoir
screens will not be required except to provide
inlet air, and the system may be operated by
sprinkler flow switch and manually by fire-
fighters.
7.2.5 The minimum layer depth used in a design cannot
be less than l0% of the building (room) height,
due to the presence of the ceiling jet in the
smoke layer (see Appendix 2 Reference 7).
10.03.94
SVAIND3.394
----------------------- Page 15-----------------------
- 12 -
7.2.6 Where the floor level changes within a
compartment, the height of rise should be
measured from the shallowest end for safety
purposes and the overall height from the
deepest end for the calculation.
7.2.7 In unsprinklered warehouses, the current fire
experience has been the total involvement, and
subsequent loss, of the building. The speed of
fire growth in all but the least combustible of
materials (eg. steel) is such that venting is
ineffective for practical considerations of
stock protection and fire-fighting operations.
See 9.2 below.
8 SMOKE COMPARTMENT
8.1 Buildings without Mezzanine Floors
8.1.2 Where required smoke compartments should have
a maximum area of 2000m² for life safety
purposes to 3000m² for other purposes with the
latter used only in exceptional circumstances
(see Appendix 2 Reference 8).
8.1.2 When used for personnel protection the maximum
length of any side of a smoke compartment in the
direction of escape should be 60.0m
(see Appendix 2 Reference 6).
8.1.3 Smoke curtains should terminate 500mm below the
design smoke layer base.
8.2 Buildings with Mezzanine Floors
8.2.1 Where reservoir limitations are required below
the mezzanine as part of the design, the
parameters given in 8.1 above should be applied.
When the design philosophy applied is to allow
the smoke to spill into an adjoining area, care
must be taken not to exceed the total reservoir
size of 2000 to 3000m² maximum.
The size of the reservoir is the combined total
of the under mezzanine floor smoke control zone
plus the area of the smoke control zone into
which the smoke is designed to flow.
10.03.94
SVAIND3.394
----------------------- Page 16-----------------------
- 13 -
9 SPRINKLERS
9.1 Industrial Buildings Excluding High Racked Storage
Warehouses
Whilst it is generally agreed that the operation of
sprinklers will reduce the fire size and the amount
of heat released, current research shows that where
sprinklers and smoke vents are installed, the operation
of the ventilators in any one compartment does not
delay significantly the activation of sprinklers
(see Appendix 2 References 7 and 9).
The effect of the sprinklers on the temperature and
buoyancy of the smoke must be allowed for in the design
of the smoke extraction system, as the smoke may have
to pass through several rings of sprinklers before
being exhausted (see Appendix 2 Reference 10).
The designer should specify the allowances made for
sprinklers in the calculations.
9.2 High Racked Storage Warehouses
Unsprinklered high racked storage buildings have been
commonplace, but due to the fire experience in such
environments are now becoming less freguent. However,
if a design is required for such a building the fire
risk will be substantial, and experience has shown that
smoke ventilation has provided very limited additional
escape time, sufficient to save lives, but cannot be
depended upon to aid the fire brigade in fighting the
fire. Flashover in these circumstances is almost
certain to occur. The smoke ventilation system designer
should strenuously recommend the installation of a
sprinkler system.
The effect of sprinklers in a high bay warehouse has to
be considered in more detail than in other situations.
The type of sprinkler heads must be considered, eg.
Early suppression fast response ceiling mounted (ESFR)
Ordinary response ceiling mounted
Ordinary response in-rack
Fast response in-rack
10.03.94
SVAIND3.394
----------------------- Page 17-----------------------
- 14 -
The operating temperature of such heads must be
considered. Typical temperatures are.
68 degrees centigrade
93 degrees centigrade
141 degrees centigrade
The spacing of the sprinkler heads, eg.
Every storage level
Alternative storage levels
Roof level only
A combination of any of the above
Al1 of the above are alternatives and will affect the
design fire size. The designer should state within his
calculations what assumptions have been made.
9.2.1 Ceiling Level Sprinklers
Ordinary Response
With ordinary response ceiling mounted sprinklers
only, the water sprays will find it difficult to
penetrate into the middle of the racks.
Extinguishment will depend on water trickling
into the main seats of fire, with the consequence
that higher water flow rates will be needed.
Fire can be expected to "burrow" through shielded
areas of fuel until it reaches parts where
sprinklers are not yet wetting,the racks. At this
point the fire will flare up and set off more
sprinklers.
This behaviour was observed in some of LPC's
High-Piled palletted fires for the CEA. The
design fire size will be as hazard category 5
of Table 1 (see Section 4).
9.2.2 ESFR Sprinklers
Research carried out by others has indicated that
ESFR sprinklers appear to provide the best means
of control for a ceiling mounted system, for
buildings up to 12m in height. At or below this
height the design of the smoke control system can
be treated as for an in-rack sprinkler system.
There appears to be no research on the efficiency
of these systems above this height.
10.03.94
SVAIND3.394
----------------------- Page 18-----------------------
- 15 -
It therefore seems reasonable to treat the
sprinklers as being more effective than ordinary-
response ceiling mounted systems, but less
effective than in-rack systems. In which instance
the design fire size adopted may be taken as a
mean value between the two.
The heat flux generated by the fire becomes less
important, as the effect of the sprinklers will
be to reduce the smoke layer temperature, and in
turn the smoky gas buoyancy. This must be
considered when natural ventilators are to be
installed, and the smoke layer temperature rise
above ambient should be limited to the minimum
sprinkler operating temperature minus ambient air
temperature. When mechanical ventilators are to
be used, it is recommended that a maximum of 50o
of this cooling should be considered. (This is
the average of the maximum calculated temperature
plus the sprinkler operating temperature).
The designer must state the degree of cooling
caused by the sprinklers which has been allowed
for in the calculations. Where there are extended
reservoir sizes (or no reservoir at all)
calculations of the additional heat lost from the
layer beyond the zone of sprinkler activity must
be stated.
9.2.3 In-Rack Sprinklers
Where there are sprinklers mounted in-rack, the
flame front rising up the rack may pass some
sprinkler heads before they operate. This effect
is particularly marked for face ignition. This
could lead to a fire which may be controlled, but
not extinguished, by the sprinklers when they do
operate, and the fire is likely to continue
burning.
In high racked fires the rising gases become
"channelled" by the flues formed by the racks.
The fire plume effectively has vertical sides
corresponding to the flues. The pattern of smoke
movement may be complicated by some smoke
spreading horizontally beneath shelves, but the
plume will rarely spread beyond a 2 bay width. It
does not spread at an angle of 15 degrees from
the vertical as is assumed for most axisymmetric
plumes in single storey buildings.
10.03.94
SVAIND3.394
----------------------- Page 19-----------------------
- 16 -
Heat may be generated through a significant
height of the rack, even when the fire is being
controlled by the sprinklers. This suggests a
useful analogy with the "Thomas" large-fire
plume, since its original derivation was for
those parts of a flame plume where combustion was
taking place in the gas phase, ie heat was being
generated throughout the height of plume. This
has the advantage that the large fire entrainment
model for a single storey building may be used.
The height of rise used should be taken as the
height from the lowest possible seat of fire (ie
usually the floor) to the base of the smoke
layer, and the perimeter of the fire must be that
part of the fire open to the air being entrained.
In practice this means that where the fire is in
the middle of a long rack, the only contribution
to the perimeter will come from the front 'face
of the rack (or if the fire is able to burn
through to both faces, from both front and back
faces of the rack). The lateral extent of fire
spread is less easy to assess, but should be
assumed to be the lateral separation between
sprinkler heads or two bay widths, whichever is
less - in most instances around 3m.
The fire 'size should therefore be taken as
either.
(a) One side of rack affected only
(b) Both sides of rack affected
The perimeter described by (b) should be used in
all cases. The only exceptions are when there is
a physical separation between the two faces of a
rack or when fast-response in-rack sprinklers are
installed to the precise specification and within
the limitations (experimental) laid down by the
FRS (Appendix 2 References 11-14) in these cases
perimeter (a) can be used.
During in-rack sprinkler tests at Cardington,
casual observation by FRS staff of the amount of
shimmer at a metre or two above the top of the
12m test rack suggested a gas temperature of
200C ± 50C when sprinklers were operating in-
rack. This estimate was unfortunately not
supported by any instrumentation at the time,
since it lay outside the design objectives of the
particular experiments. It is hoped that further
research will yield better data.
10.03.94
SVAIND3.394
----------------------- Page 20-----------------------
- 17 -
There is no indication that fire will progress
further up the racks, hence this value can be
taken as a limiting parameter, with the heat flux
being generated over a 12-14m height. Using the
previously described values of fire perimeter,
and the mass flow equation, the convective heat
flux generated can be approximated.
Where ceiling sprinklers are installed, either
complementary to, or in replacement of the
topmost in-rack sprinkler level, the final gas
layer temperature must be limited as described in
9.2.1 above, prior to further calculation of any
losses due to extended reservoir sizes.
10 DEPTH OF SMOKE LAYER
10.1 Industrial Buildings Excluding High Racked Storage
Warehouses
In order to avoid the risk of "flashover", sufficient
ventilation should be provided to ensure the smoke
layer temperature does not exceed 600C for the design
conditions (see Appendix 2 Reference 2). However, the
smoke layer depth cannot be less than 10% of the
building (room) height. Where this occurs
consideration should be given to other (additional)
forms of protection, eg sprinklers.
10.2 High Racked Storage Warehouses
10.2.1 Since it is extremely unlikely for an
unsprinklered high racked storage area to
survive a fire, the following applies to areas
which are sprinklered, where flashover is not
likely to occur. However, flashover should
alvaays be considered, as this guide
recommends.
As the smoke layer base will be in many
instances, by design, at a high level within
the building, it is likely that cool smoke
temperatures will result, especially if
extended reservoirs are employed.
Smoke temperatures less than approximately 20
degrees centigrade above the average roof level
ambient temperature have resulted in the smoke
layer de-stratifying and mixing downward with
the ambient air beneath. This is mainly due to
weak cross-draughts and convection currents,
and will occur despite the provision of a smoke
extraction system. This scenario must be
considered by the designer.
- 18 -
10.03.94
SVAIND3.394
----------------------- Page 21-----------------------
10.2.3 The cooling effect of the operation of the
sprinklers must be considered, refer to
9.2 above.
The designer must state the degree'of cooling caused
by the sprinklers and extended layer travel which has
been allowed for in the calculations.
11 AMBIENT TEMPERATURE
o
For smoke venting calculations a figure of 288 K should be
used (see Appendix 2 Reference 8).
12 AIR INLETS/REPLACEMENT AIR
12.1 For any scheme to be effective, sufficient replacement
air must be provided in order that extract ventilators
operate properly (see Appendix 2 Reference 6).
12.2 Doors and windows, as well as ventilators, can be used
for replacement air. However, if intended for use in
this way the'y should be fitted with automatic
controls compatible with the system. The designer
should state the ratio of extract to inlet area used
in his calculations.
12.3 To avoid disruption of the smoke layer in any single
compartment, the base of the smoke layer should be at
least 1-2m above any door/opening which might either
by design or chance be a source for replacement air,
unless the incoming air velocity is less than lm/s, in
which instance it should be no less than 500mm above
the opening.
12.4 The design inlet velocity shall not exceed 5.0m/s.
12.5 Ideally, replacement air should be introduced at
low level from all directions. However, natural
ventilators in the non-fire compartments can be used
if smoke curtains/screens are fitted to prevent short
circuiting.
12.6 Powered ventilators can be used for replacement air.
Care should be taken as they may cause turbulence
which can increase smoke/fire spread.
12.7 Where security bars, "insect" mesh or bird screens are
fitted, the effect of these should be considered when
determining the ventilator discharge coefficient.
- 19 -
10.03.94
SVAIND3.394
----------------------- Page 22-----------------------
13 WIND EFFECTS
The designer should consider the effect of wind pressures
on smoke extraction systems.
Information published by the Building Research
Establishment and BSI (CP3, chapter V pt 2) shows for a
building considered in isolation, natural ventilators will
o
be subject to negative pressure of roof slopes of 30 , or
less, from the horizontal.
Installations of natural ventilators on roofs over 30 from
the horizontal should not be considered without some form
of baffling unless supporting data from wind tunnel tests
and/or computer simulation is available. This baffling can
be external to the unit or part of the ventilator design.
When changing wind directions may cause positive or
negative pressure fluctuation in the building structure,
natural extract ventilators should be installed in
sufficient numbers and positions and controlled via wind
sensor/pressure monitors to ensure that an appropriate
number open at any one time.
If in doubt about pressure distribution on the building
structure, a powered system should be used.
Snow loadings should also be considered when designing/
siting of both powered and natural supply/extract systems.
Any effects caused by the wind which may affect the smoke
ventilation system proposed, must be clearly stated by the
designer.
14 SPECULATIVE BUILDINGS
This is not, relevant to Mezzanine Floors or High Racked
Storage Areas since it is extremely unlikely that such a
building would be built speculatively.
Where designers are called upon to design systems for
buildings where details of the occupancy, use, sprinklers
etc. are unavailable, the following minimum criteria should
be used for design.
14.1 4.5m x 4.5m sprinklered fire (see Sections 5.3 and
5.4 for heat output).
14.2 Clear layer to eaves level or 500mm above the top of
the highest opening.
14.3 Replacement air not available from doors and windows.
14.4 Smoke compartments to be limited to 2000m² max.
- 20 -
10.03.94
SVAIND3.394
----------------------- Page 23-----------------------
15 SIZING / SITING OF EQUIPMENT
All smoke control products should comply with the
requirements of the "SVA Guide to good practice on
application of smoke control equipment and systems" (see
Appendix 2, Reference 15). Extract equipment should
not exhaust at a rate likely to puncture the smoke layer
and should be sited in such a way as to not disturb the
smoke layer base. Particular consideration should be given
to High Racked Storage Areas since the smoke layer depth
is freguently very shallow in these buildings. (In this
context) mass flow rate and velocity should be considered
(see Appendix 2 References 16 and 17).
Rules used in the Industry are:
15.1 The size of natural and powered extract units should
be limited to prevent puncture of the smoke layer.
Reference 16, Appendix 2 shows methods of calculation
and limiting factors.
15.2 Natural extract ventilators should not be spaced
morethan 20m apart.
15.3 For natural systems, the preferred aerodynamic area
Of inlet should be at least equal to the aerodynamic
areaof extract. The designer should state the actual
ratio taken into account in calculations.
15.4 For mechanical systems, inlet resistance should be
considered when sizing equipment extraction and the
value should be stated by the designer.
15.5 Fan motors should be rated at temperatures compatible
with the system design, but should be sized to
operate at ambient conditions (288K).
15.6 Compressed air receivers should be capable of three
operations of the system after power failure.
15.7 Exhaust equipment should meet the specifications of
the relevant British Standard (see Appendix l,
References 3 and 4).
16 CONTROLS
Controls form an integral part of the system design.
16.1 A smoke extract system is operated by an automatic
control system, which may be activated by any of the
following:
Smoke detection; heat detection; sprinkler flow
switch; manual alarm.
- 21 -
10.03.94
SVAIND3.394
----------------------- Page 24-----------------------
The preferred system is activation by zoned smoke
detection.
16.2 Ventilators operated only by a fusible link/thermal
device do not constitute a smoke extract "system".
16.3Power system controls and their connections should
maintain their integrity under design conditions in
a fire and should be designed to "fail" in the "on"
position.
16.4 Zone Control - The time taken for all ventilators
within a fire compartment to be fully operational
must not exceed 60 seconds from system
activation/smoke detection.
16.5 For natural ventilators used for life safety
purposes, in the event of power/system failure, the
equipment must failsafe in the "open" position.
17 MEZZANINE FLOORS
The effect of a mezzanine floor on smoke flow is not only
to induce more air entrainment but also to result in larger
quantities of cooler smoke. Therefore, there are additional
requirements when considering the smoke free clear layer to
ensure that the upper levels of the building remain free of
smoke for escaping people.
17.1 Clear Layer
The minimum clear layer, wherever possible, to the
underside of the smoke layer shall be.
3.0 metres above the floor level where the smoke is
contained to the floor or origin.
OR
3.0 metres above the uppermost occupied level of
mezzanine floor level where the smoke is allowed to
spill out from under the mezzanine floor:
1.0 Life safety, ie escape travel distances.
2.0 Smoke layer temperature, ie will "flashover"
occur.
3.0 Stock protection, ie maintaining a clear layer
above stored products.
- 22 -
10.03.94
SVAIND3.394
----------------------- Page 25-----------------------
Smoke which has travelled laterally beneath a solid
mezzanine floor with entrain additional air as it
rotates around the balcony edge. Further entrainment
will occur as the smoky gases rise to the smoke
reservoir. The amount of entrainment is dependant upon
the width of the plume of smoky gases at the edge of
the mezzanine floor and the height of smoke must rise
from the mezzanine floor to the underside of the smoke
layer.
Thus, it is clear that the type of mezzanine floor may
affect the quantity and temperature of any smoke to be
extracted. For smoke control design purposes there.are
only two mezzanine types to be considered, Open
Mezzanine Floors and Solid Mezzanine Floors.
17.2 Permeable Mezzanine Floors
A mezzanine floor level within a single storey
industrial building is deemed to be a permeable
mezzanine floor if there is at least 25% free area of
the total floor plan area (not around the edge) evenly
distributed as openings over the whole floor area (see
Appendix 2 Reference 16). The calculation to determine
the free area should be the total floor plan area less
all obstructions to smoke flow through the mezzanine,
for example offices, storage areas, flooring material
etc.
If, by calculation, it can be proved that the
mezzanine floor has, and will continue to have, at
least 25% free area, then for smoke control purposes
it does not exist, since it has been proved that false
ceilings with this amount of free area do not
appreciably interfere with the flow of hot smoky
gases.
The design philosophy and methodology given in the
main body of this document shall apply, with the
proviso that the clear layer shall be, wherever
possible, at least 3.0 metres above the upper occupied
mezzanine floor level.
The smoke control designer shall ascertain whether the
25% criteria can be met initially, and advise his
client of the relevance and importance of the figure.
The smoke control system commissioning and maintenance
documents should also refer to the critical nature of
the 25% criteria, in an attempt to ensure that this
figure will not be reduced in the future.
- 23 -
10.03.94
SVAIND3.394
----------------------- Page 26-----------------------
17.3 Solid (Non Permeable) Mezzanine Floors
Where mezzanine floors are solid or do not meet the
requirements of a permeable mezzanine floor, the
following design methods shall be applied.
There are two alternative design approaches which can
be considered for this type of mezzanine; containment
of the smoke to the floor of origin or to allow the
smoke to spill around the mezzanine floor edge and
rise to the roof smoke reservoir. The design
considerations for these alternative methods are
completely different and therefore these have been
shown separately.
17.3.1 Containment
This approach can be applied to the control of
smoke under solid mezzanine floors. Smoke from
a fire under the mezzanine is prevented from
spilling out of the area into the single
storey part of the building by means of smoke
curtains/screens, and is extracted from this
level.
In this instance, the recommendations
contained in the main body of this document
shall apply. However, due consideration shall
be given to both the smoke layer temperature,
(which may be high enough for flashover to
occur due to the limited height of rise from
the fire base to the underside of the smoke
layer), and the necessary depth of the smoke
curtains/screens required to prevent the
spillage of smoke from the area of containment
(which may, due to their depth, hamper
escape). Furthermore, the extract equipment
shall not exhaust at a rate likely to puncture
the smoke layer, as detailed within Sizing/
Siting of Equipment section of this document.
17.3.2 Smoke Flowing beyond a Mezzanine Floor Edge
As has been stated above, entrainment of air
into the smoke plume will occur as the smoke
spills about the edge of the mezzanine floor.
The amount of entrainment, and hence the mass
and temperature of the smoke to be extracted,
is dependant upon the following factors.
1 The height to the underside of the
mezzanine floor above the fire base.
- 24 -
10.03.94
SVAIND3.394
----------------------- Page 27-----------------------
2 The depth of beam at the open edge of
mezzanine floor.
3 The width of the plume of hot smoky gases
at the edge of the mezzanine.
4 The height of rise of the smoke from the
underside of the mezzanine floor to the
bottom of the smoke layer.
5 The geometry of the rising plume of smoky
gases.
17.3.2.1 The Height to the Underside of the
Mezzanine Floor above the Fire Base
Consideration, must be given to the factors listed
within Section 7 of this document. It should be noted
however that since the smoke is not being contained
under the mezzanine but allowed to spill out of the
area, it is the determination of the flowing smoke
layer (its depth and its temperature) that are
critical. Relaxation of the minimum clear layer may
need to be sought in some circumstances.
The worst case of smoke generation must be
considered.
Research and evidence from real fires has shown the
largest quantity of smoke is produced when the
distance between the fire base and the underside of
the smoke layer is greatest. Thus, a fire should
always be considered as occurring on the lowest floor
level.
The amount of entrainment of air into the rising
plume of smoke beneath the mezzanine is dependant
upon its height of rise, ie from the fire base to the
underside of the flowing smoke Iayer.
The designer must state within the
calculations what criteria has been allowed.
17.3.2.2 The Depth of Beam at the Open Edge of
Mezzanine Floor
Research carried out, particularly in the areas of
smoke flowing under balconies in shopping centres and
atria buildings, has shown the importance of the
balcony or edge beam in the amount of entrainment
which occurs into the flowing smoke layer.
- 25 -
10.03.94
SVAIND3.394
----------------------- Page 28-----------------------
It must be determined whether or not the edge beam is
"deep", relative to the flowing smoke layer (see
Appendix 2 References 2 and 16).
The designer must state within the
calculations what criteria has been allowed.
17.3.2.3 The Width of the Plume of Hot Smoky Gases
at the Edge of the Mezzanine
The amount of additional entrainment into the rising
plume of gases is related to the width of the plume of
smoke as it rotates about the mezzanine floor edge.
The use of void edge smoke curtains or screens to
limit this width is recommended in most instances.
The depth of these smoke curtains/screens should,
wherever practical, be 500mm below the depth of the
flowing smoke layer beneath the lowest transverse
obstruction to the smoke flow.
The designer must state within the
calculations what criteria has been allowed.
17.3.2.3 The Height of Rise of the Smoke from the
Underside of the Mezzanine Floor to the
Bottom of the Smoke Layer
Further entrainment into the smoky gases will occur
as the plume rises from the point at which it has
spilt out from under the mezzanine floor up to the
reservoir of smoke at roof level.
The amount of additional air which is drawn into the
rising plume is dependant upon its height of rise and
its geometric shape as detailed below.
Wherever possible the minimum height of rise of the
smoke plume shall be 3.0 metres above the uppermost
occupied level of mezzanine floor.
The designer must state within the calculations what
criteria has been allowed.
17.3.2.4 The Geometry of the Rising Plume of
Smoky Gases
Air can only be drawn into the rising plume of gases
on those faces of the gas stream which are in open
space. The smoke plumes are normally considered to
have four sides, a front, back and two ends.
- 26 -
10.03.94
SVAIND3.394
----------------------- Page 29-----------------------
It will be noted therefore that there are a number of
configurations of smoke plumes to be considered, all
of which will introduce different quantities of air
into the rising smoky gases.
The designer must state within the calculations that
criteria has been allowed.
Single Sided Plume
This is rarely found since it can only entrain air
into one of its four sides, normally its front. For
this to occur, the plume must be as wide as the smoke
curtains/screens which limit its width (and be
prevented from increasing by the building structure),
and the rear of the plume must rise adjacent to the
face of the building structure.
Single Sided Plume with One End
This type of plume is also unusual, since the smoke
plume will rise with one end and either the front or
rear face adjacent to the building structure.
Single Sided Plume with Both Ends
This is one of the most common types of rising smoke
plumes from under mezzanine floors.
Smoke spilling out from under a mezzanine floor and
rising in free air except for the rear of the plum
which is adjacent to the structure of the building.
Two Sided Plume with Both Ends
The most common of smoke in this type of building,
and also the one which results in the largest mass of
coolest smoke to be extracted.
The stream of smoky gases from under the mezzanine
rises without restriction in free air.
10.03.94
SVAIND3.394
----------------------- Page 30-----------------------
- 27 -
APPENDIX 1 - ASSOCIATED BRITISH STANDARDS
1 BS 4422. Part 5. 1988
ISO 8421 - S. 1988
Terms associated with fire, part 5, smoke control
2 BS 7346. Part 3. 1990
Components for smoke and heat control systems
Specification for smoke curtains
3 BS 7346. Part 1. 1990
Components for smoke and heat control systems
Specification for natural smoke and heat exhaust
ventilators
4 BS 7346. Part 2. 1990
Components for smoke and heat control systems
Specification for powered smoke and heat exhaust
ventilators
10.03.94
SVAIND3.394
----------------------- Page 31-----------------------
- 28 -
APPENDIX 2 - REFERENCES
1 Theobald, C. Studies of Fires in Industrial Buildings
Part 1. The Growth and Development of Fire, Fire Prev
Sci. Technol, 17 (1977) pp 4-14.
2 Morgan, H P and Hansell, G O. Atrium buildings :
calculating smoke flows in atria for smoke control design.
Fire Safety Journal, 12 (1987) pp 9-35.
3 National Fire Protection Association. Smoke Management
in Malls, Atria and Large Areas. NFPA 92B. Quincy, M A.
NFPA (1991).
4 Thomas, P H et al. Investigations into the flow of hot
gases in roof venting. Fire Research Technical
Paper No. 7. HMSO, London (1963).
5 CEN Task Group Committee. Private Communications.
CEN/TC191/WG8/TG3, Design and Calculation Methods for
Smoke and Heat Exhaust Ventilation Systems, Brussels
(Dec 1993).
6 Thomas, P H et al. Design of roof venting for single
storey buildings. Fire Research Technical Paper No. 10,
HMSO, London (1964).
6 Hinkley, P L. The effect of vents on the opening of
The first sprinklers. Fire Safety Journal 11 (1986)
Pp 211-225.
8 Morgan, H P. A simplified approach to smoke venting
calculations. Building Research Establishment
information paper IP 19/85, BRE, Garston (1985).
9 Hinkley, P L et al. Experiments at the Multifunctioneel
Trainingcentrum, Ghent,0n the interaction between
sprinklers and smoke venting. Building Research
Establishment Report No. BR 224(1992), BRE,
Garston (1992).
10 Heselden, A J M. The interaction of sprinklers and roof
venting in industrial buildings the current knowledge.
Building Research Establishment.
11 Field, P. -How in-rack sprinkler protection was developed
for Donnington. Fire V79(973) (1986) pp 47-48.
12 Field, P. Effective sprinkler protection for high-racked
storage. Fire Surveyor 14(5) (1985) pp 9-25.
10.03.94
SVAIND3.394
----------------------- Page 32-----------------------
- 29 -
13 Murrell, J V and Field, P. Sprinkler protection for post-
pallet storage in high racks. Fire Surveyor 19(1) (1990)
pp 16-20.
14 Murrell, J V and Field, P. Selection of sprinklers for
high-rack storage in warehouses. Building Research
Establishment Information Paper IP 5/88. Fire Research
Station, Borehamwood (1988).
15 Smoke Ventilation Association. SVA Guide to good practice
on application of smoke control equipment and systems.
Federation of Environmental Trade Associations,
Bourne End (1994).
16 Heselden, A J M. Efficient extraction of Smoke from a
thin layer under a ceiling. Fire Research Note No. 1001,
Fire Research Station, Borehamwood (1974).
17 Morgan, H P and Gardner, J P. Design principles for smoke
ventilation in enclosed shopping centres. Building
Research Establishment Report No. BR 186, BRE,
Garston (1990).
10.03.94
SVAIND3.394
----------------------- Page 33-----------------------
- 30 -
APPENDIX 3
GROUP 1
CLASSIFICATION OF SPRINKLER CATEGORIES FOR INDUSTRIAL BUILDINGS
Breweries (excluding bottling sections) Restaurants and cafes
Power Stations
Butchers' slaughter houses
Creameries and wholesale dairies Abrasive wheel and power
manufacturers Cement works
Jewellery factories
GROUP 2
Bakeries and biscuit manufacturers
Chemical works with little fire hazard
(otherwise Group 3 or 4)
Motor car repair shops and large motor garages Motor vehicle
and accessories manufacturers Food - and preserved food
manufacturers
Machine factories including light metal manufacturers
GROUP 3
Cotton spinning mills
Bleacheries, dye-works
Brandy distilleries
Brush manufacturers
Printing offices
Tanneries,1eather good manufacturers
Cereal mills, grinding and peeling mills
Rubber and rubber articles manufacturers(excluding foam rubber)
Flax, jute, hemp mills
Aircraft manufacturers (excluding hangars)
Plastic and plastic products manufacturers (excluding foam)
Cardboard, paper and paper products manufacturers
Radio and television manufacturers (and appurtenances)
Sawing mills and wood using manufacturers
(including furniture factories)
Soap and wax products manufacturers
Textiles and carpets manufacturers
Sound, radio, film and television studios just as
Broadcasting rooms
Wool and worsted mills
Sugar works and refineries
- 31 -
10.03.94
SVAIND3.394
----------------------- Page 34-----------------------
GROUP 4
Manufacturing and/or working up.
Celluloid
Paint, sealing wax, resin, turpentine, soot, tar Fire works,
lighting goods
Floor covering, linoleum etc
Aircraft hangars
Wood-wool Oil mills
Foam rubber, foam goods
GROUP 5
Warehouses with racking for combustible and non-combustible
materials in combustible packing. Not high bay warehouses or
palletised stock etc, as these are covered by other procedures.
SUB-DIVISION OF GROUP 5
GROUP 5/l
(Combustible and non-combustible materials in combustible
packing)
Electrical apparatus
Presswood boards
Glass and ceramic goods
Textiles
FoodMetal goods
Carpets
GROUP 5/2
Bottles with alcohol (packed in cardboard)
or alcohol in barrels
Pharmaceutical goods and cosmetics
Paper, cardboard
Roo£ing felt (tarred board) (stacked horizontally)
Veneering boards or timber
Furniture
Cork
Plastic products (excluding foams)
Varnish in tins (packed in cardboard)
Paper rolls (stored horizontally)
Floor covering
- 32 -
10.03.94
SVAIND3.394
----------------------- Page 35-----------------------
GROUP 5/3
Roofing felt in rolls (stored vertically)
Rubber goods
Wood goods
Oil and wax paper
Cardboard and paper rolls (stored vertically)
Foams and plastics (packed and unpacked) and all
products packed in foam material
Cellulose
Wooden pallets, wooden battens and well aerated
stacks of wood
Celluloid
GROUP 5/4
Scraps of plastic or foam rubber, stored foam rolls and
latex foam rubber
10.03.94
SVAIND3.394
----------------------- Page 36-----------------------
- 33 -
APPENDIX 4 - RATES OF HEAT RELEASE FOR VARIOUS FUELS
OF A KNOWN HEIGHT
TABLE A4.1 STORAGE RISKS
RHR (kW/m2)
Fuel
Stored Products Height
UK USA
(m)
Data Data
Wood crib 290 -
Wood crib 544 -
Wood crib 990 -
1582 -
Wood crib
- 1250
Wood pallets, stacked - 3500
Wood pallets, stacked - 6000
Wood pallets, stacked - 9000
Wood pallets, stacked 28
Crated furniture 82
Stacked sawn timber 134
160
Stacked chipboard
Cellulosics generally
- 350
Mail bags 524 -
Stacked cardboard 840 -
Cardboard reels 1030 -
Cardboard cartons - 1500
Cartons, compartmented, stacked 284 -
Cartons, electrical, goods 1130 -
Packaged goods - 870
Fibreglass components in cartons
PE fibreglass shower stalls in - 1250
cartons, stacked
Plastic bottles in cartons, - 4320
stacked
PVC bottles packed in cartons, - 3000
compartmented, stacked
PE bottles in cartons, - 5500
compartmented stacked 1750
PE bottles in cartons, stacked - 7500
PE letter trays, filled, stacked
PE trash barrels in cartons, - 1750
stacked - 4200
Plastic films in rolls - 5500
PP & PE films in rolls, stacked
PP tubs packed in cartons - 3900
compartmented, stacked
10.03.94
SVAIND3.394
----------------------- Page 37-----------------------
- 34 -
APPENDIX 4 - RATES OF HEAT RELEASE FOR VARIOUS FUELS OF
A KNOWN HEIGHT
TABLE A4.1 Continued
RHR (kW/m2)
Stored Products Fuel
UK USA Height
Data Data (m)
PU Insulation packed, stacked - 1210 4.6
PU Insulation boards, rigit
foam in cartons, compartmented,
stacked - 1700 4.6
PS Insulation boar, rigid foam,
stacked - 2900 4.3
PS jars in cartons* - 12400 4.6
PS jars packed in cartons
compartmented, stacked* - 12500 4.6
PS tubs in cartons - 3450 4.3
PS tubs nested in cartons,
Stacked - 4750 4.3
PS toy parts in cartons - 1400 4.6
PS toy parts in cartons, stacked - 1800 4.6
Books, furniture 2160 - 3.0
NB These figures appear to be anomalously high compared
With those following in the next four rows, which are
essentially the same product.
TABLE A4.2 SPECIFIC RISKS
RHR (kW/m2)
Fuel
Height
Stored Products
(m)
UK USA
Data Data
Furnished Offices 230 - -
Workshops for vehicles, petrol,
Paint 260 - -
Garages for trucks 1860
10.03.94
SVAIND3.394
----------------------- Page 38-----------------------
- 35 -
TABLE A4.3 LIQUID FUEL RISKS
RHR (kW/m2)
Fuel
Height
Liquid Fuels
(m)
UK USA
Data Data
Industrial methylated spirit 740 650 -
Gasoline, petrol 1590 - -
Light fuel oil 1470 - -
10.03.94
SVAIND3.394